RESIDENTIAL SERVICE
REQUIREMENTS
GENERAL REQUIREMENTS
This chapter provides you with general requirements for the metering
equipment that you need in order to have your service energized. Your meter base
needs to meet the following criteria for our meter to properly connect.
No meter base will be energized until our crews can see that the inside breaker box has a permanent metal cover installed and secured. (This may be waived if there is an external main disconnect switch installled.)
Your meter base and other equipment installation must meet the requirements of your local electrical inspector. If you have specific questions regarding your meter installation please contact your local electric inspection agency (see page 4).
Meter bases may not be covered by any stucture, unless it can be moved without the use of tools to allow full access to the meter.
SERVICE RATING OPTIONS
As stated in SECTION A - GENERAL INFORMATION, Central
Lincoln’s metering equipment requirements for
single-family residential structures (not apartments or condominiums) are
based upon the following single-phase service ratings [and the customer must
select which amperage rating is required for the project]:
Ampere Rating Voltage 200 Amp 120/240 400 Amp 120/240 over 400 Amps* 120/240 * If you need a service over 400 amps or a three phase service, please contact your nearest service office (see appendix). Those services will be addressed individually and are not covered in this handbook.
You are responsible for providing and installing all equipment other than:
METER BASE REQUIREMENTS
The meter base you purchase and install must meet the following general
requirements. (Specific requirements for 200 and 400 amp services, and for
outbuildings, are listed later in this chapter.)
Your meter base must be:
200 AMP SERVICE
The 120/240 volt, 200 ampere service is the most common service installed
by CLPUD. Typically it’s installed in homes with a living area of less than 2500
square feet. However, depending upon
what type of equipment you are installing
you may want a larger service. It is your responsibility to determine your
electrical requirements and to notify CLPUD of the size of service you would
like.
Meter bases for 200 amp services shall also:
The center knockout should not be used on underground because of the bending radius of the cable.
If your outbuilding or ancillary service will be used for commercial purposes (i.e. a professional shop, dairy barn, illuminated sign, multifamily/community well) you will have additional requirements. If this is the case please refer to the Central Lincoln Electric Service Handbook for Non-Residential Services.
GROUNDING REQUIREMENTS
All meter bases and conduit shall be bonded and grounded in accordance
with the NEC.
New construction shall have a "UFER" ground installation poured in
the footings and be inspected by the building official. It is your
responsibility to coordinate this installation with the proper authorities and
receive their approval.
CLEARANCE REQUIREMENTS
The following clearances are required around all meter installations. It
is your responsibility to provide and maintain these clearances.
400 AMP SERVICE
The meter base required for a 120/240 volt, 400 ampere service is a
"Class 320" meter base (see Figure D-4). It is larger than the 200 amp meter
base, but it is still a self-contained meter base (it doesn’t require instrument
transformers). It can be installed on residences where the continuous current
rating is 320 amps or less. If your structure will require more than 320 amps
continuous, you are required to install an instrument transformer (CT or PT)
service.
Class 320 meter bases for 400 amp services shall, in addition to the meter base requirements listed above;
400 AMP CT SERVICE
CT services are also known as "instrument transformers". You may request
a 120/240 volt, 400 amp CT service, available at an additional charge. This
service requires a different meter base (see Figure D-6). It also requires
additional equipment (CT enclosure, conduit, CT mounting bracket, etc.). Contact
our nearest service office (see
SECTION A - GENERAL INFORMATION) and ask to speak to the meter
department.
Phase Service
AmperageCTs Dimensions No. of Transf. W H D 1 401-800A 2 24" 24" 11" 3 201-400A 3 36" 36" 11"
SERVICES OVER 400 AMPS
120/240 volt services over 400 amps require CT metering. Please contact
your nearest service office and ask to speak to the meter
department for more
information.